Hydrogen Detector with Remote Sensor 7200R
Because these detectors are custom made to individual application, all sales are final. No returns or refunds available after purchase.
Specify range desired when placing order: 0-250, 0-1000, 0-10000, 0-20000 (50% LEL) ppm
Features
- Continuous 24 hour monitoring
- Compact, and durable unit
- Explosion proof housing for remote sensor
- Audio/Visual alarms and relay contacts
- Malfunction alarm and Test/Checking alarm set switches
- Infrequent maintenance and calibration required
- Remote sensor reliable to 600 feet from controller
- Solid-state (PPM), Catalytic (% LEL) sensors, fast warm-up time
- Optional recorder terminals
The wall-mounted toxic gas or combustible gases detector with audio/visual alarms and relay contacts provide continuous open/enclose space monitoring. The basic unit has a detecting sensor and controller joined together. if necessary, remote sensor with explosion-proof junction box housing and 50 feet cable wire (longer length can be extended to 600 feet) connection are also available. The explosion proof sensor and housing are ideal for hazardous area monitoring and meet NEC requirements for Class I, Division I, Group A-B-C-D. All the models can provide either 4-20mA or 0-10 VDC output for data acquisition purpose, and PLC Interfacing. Analog meter indicates PPM or % LEL. Digital meter use large red LED is also available.
Each detector includes sensor and controller (R-type includes housing and 50 feet cable wire). Standard model includes meter (ppm or % LEL), LED alarm, audio alarm, fail alarm, check and test switches and relay contacts. Standard 2 stage wall mount model includes meter (ppm or % LEL), visual alarms & audio alarms (high, low), fail alarm, check & test switches and 3 relay contacts (low, high, fail).
Specifications:
Dimensions: | 8"H x 5"W x 4"D |
Readout Meter: | Analog PPM, % LEL, or 4 Digits large 0.3" red LED |
Temperature Rage: | -10°F to 150° |
Repeatability: | ±2% |
Power Usage: | ~3.5 Watts |
Power Input: | Standard 115 VAC or 220 VAC or 24 VDC |
Alarms Circuits: | Fail LED (yellow), Alarm LED (red), Audio Sound (steady) |
Alarm Point: | Variable setting in the meter range |
Panel Controls: | Zero, Span, Set "alarm", Test and alarm set Check switches |
Relay Contacts: | SPDT 1 A, 115 VAC or 24 VDC |
Analog Output: | (Optional) 4-20mA or 0-1 VDC |
Weight: | 2 lbs (sensor attached to controller type) 9 lbs (remote sensor type) |